pCOWeb +030220471 – rel. 1.0 – 02.05.2007 23
<VALUE></VALUE>
pCOWeb returns the current value multiplied by 10
(999.9 x 10 = 9999) of the analogue
variable with index 1
<VALUE>9999</VALUE>
</VARIABLE>
End of the section for the analogue variable with index
1
</VARIABLE>
<VARIABLE>
Start of the section for another analogue variable
<VARIABLE>
<INDEX>2</INDEX>
Specifies the index 2 for the variable to pCOWeb
<INDEX>2</INDEX>
<VALUE></VALUE>
pCOWeb returns the current value multiplied by 10
(-12 x 10 = -120) of the analogue variable
with index 2
<VALUE>-120</VALUE>
</VARIABLE>
End of the section for the analogue variable with index
2
</VARIABLE>
</ANALOG>
End of a section for analogue variables
</ANALOG>
</PCO>
End of the section with the sequences of tags with
pCO properties
</PCO>
</PCOWEB>
End of the section recognising the sequences of tags
</PCOWEB>
NOTES on using the XML standard
The syntax of a file with the .xml extension can be validated, for example, by displaying it in Internet Explorer; pCOWeb nonetheless only recognises the
syntax shown above. In particular, it does not recognise the standard XML <text /> tag, which in standard XML is equivalent to the pair <text> + <text/>.
pCOWeb does not validate the template file used.
Information, strings and tags other than those shown above can be entered in any position; if not recognised according to the syntactical limits shown in
Table 4.a on page 22, they will be copied textually without any action.
4.3.3 Setting the common properties to all events
Par.
4.3.1 on page 20 describes the operation of the notification events. Below is a description of the setting procedure.
IMPORTANT
For pCOWeb to send the notifications, normally the “Gateway” needs to be set in the network configuration (see 8.4.1 on page 39). The
gateway configuration is not however required if the address of the pCOWeb and the addresses of the receiving network devices are in the
same subnetwork. For further information see
APPENDIX B on page 53.
NOTE 1 All the following settings are valid from when they are confirmed; the pCOWeb does not need to be rebooted.
NOTE 2 The Tests page (see
8.9 on page 45) can be used to manually send all the notifications set, regardless of whether the events occur; once the events have
been set, it is recommended to check the sending of the notifications on this page.
NOTE 3 APPENDIX D on page 57, APPENDIX E on page 60 and APPENDIX F on page 61 describe some freeware applications downloadable from the Internet that,
once installed on a computer, can receive e-mails, files via FTP and TRAP messages from the pCOWeb.
These should be used for testing without requiring an external server.
PROCEDURE
1. From the pCOWeb main page (see
Figure 8.b on page 36)
open the “Events” page (click point 1 in
Figure 4.n).
2. Open the window for setting the recipients and the attached
files (click point 2 in
Figure 4.n).
The settings in this window will be common to all the events
generated.
The window is divided vertically into three areas (
Figure 4.o on
page 24,
Figure 4.p on page 24 and Figure 4.q on page 24).
Each has a confirmation button that is only valid for the
corresponding area.
Figure 4.n – Notification events page