Carel plug-in Manuel d'utilisateur Page 49

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 80
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 48
pCOWeb +030220471 – rel. 1.0 – 02.05.2007 49
2. Click “Provide firmware image”; (see
Figure 8.gg below), the page used to choose
the block A file will be displayed; select “Upload” to transfer the block to the
VOLATILE memory (during this phase the block will only be copied to the
VOLATILE memory and checked).
3. When the page showing “Upload result: Ok” is displayed, select “Press here to start
immediately”: the file will be written to NON-VOLATILE memory.
4. The end of the procedure will be signalled by the page shown in
Figure 8.hh
below; then reboot pCOWeb.
5. Wait at least 2 minutes, then load the main page by entering the name of the
pCOWeb or the IP address in the address field and pressing Enter.
NOTE After rebooting the Rescue Mode page may be displayed again. Usually this is
simply a problem with the browser.
To make sure that pCOWeb is no longer in Rescue Mode, check the Status LED; if
flashing green, the Rescue Mode page displayed is one saved in by the browser;
refresh the page by pressing Ctrl-F5; if this doesn’t work, try deleting the browser’s
cache memory, and if this still doesn’t work, close and open the browser again (all
the instances running).
If, on the other hand, Rescue Mode is still active even after rebooting pCOWeb
, there may be errors in the formatting of the non-volatile memory.
Proceed as follows (see Figure 8.ii on page 50):
Figure 8.ff – The “Rescue Mode” page
Figure 8.gg – Reloading block A
Figure 8.hh – When loaded, reboot pCOWeb
Vue de la page 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 79 80

Commentaires sur ces manuels

Pas de commentaire